Select your country
Prices Inc.Tax Excl.Tax
SP177200845

TCBT/8-800 K Ex

duct non-explosive axial fan

Price
Excl. Tax: €0 Incl. Tax: €0
out of sortiment

Fan TCBT/..Ex are axial non-explosive fan in perform „ex“, suitable for mounting into circular duct. Fans are designed for bigger flow and small pressure loss. Fans are suitable for transport of air without mechanical particles, which could cause abrasion or imbalanced of the impeller. Fan TCBT Ex are suitable for space zone 1 by standard CSN EN 60079-14/7,98 (sooner SNV 2). Can not exposed to direct effects of the weather. Fans can be mounting in vertical or horizontal position. Fan can not controlled with transformator or electric speed control. For fans with variable angle setting of the blades, the manufacturer of this set angle can not be changed. Fans should be stored in covered and dry warehouse. Fans are produced in a quality system to ISO 9001.


Speed [min-1]710
Air Flow Volume [m3/h]16600
Current [A]2.5
Power [W]870
Voltage400V
Duct diameter [mm]800
Min. temperature [°C]-40
Max. temperature [°C]40
Protection IPIP55
Noise [dB(A)]69
Description
Housing

The fan housing is made of stainless sheet, equipped with black epoxy varnish, holders and screws are galvanized plated.

Impeller

The fan impeller is made of AL. Impeller is statically and dynamically balanced, the range of operating temperature is 20-40 °C. Vanes is 32˚ or 34˚ standard.

Motor

The fan engine is asynchronous with squirrel in the short, stator with cooling ribs, black epoxid varnish with insulation class F. Ball bearing are greased to time for life. Protection IP55. By size 710 and 800 necessary consulting with our technicians IA/IN and te.

Direction of rotation

It can delivered impeller for to rotate in the opposite direction. By duct perform is standardly flow of air from impeller to engine.

Terminal block

The terminal block is in non-explosion perform and is placed on the cupboard.

Noise level

The noise emitted by fan is shown in tables, the measurement is made at a distance equal to three times the impeller diameter (minimum 1.5 m) on the suction side.

Installation

The mounting of these fan is can be in every position in axis engine. Fans HCBT can be install to the wall, exhaust and suction must stay free ( when mounted in a pipe network fails fan in terms of allowable heating). Fan housing must not transport mechanical stress from duct. Get information about special design (different angles of the vanes) and the current supplied special accessories. Ask about deadlines. Caution: the fans are special design for the Czech Republic. You can not use standard spare parts supplied by the manufacturer or other business organizations. Fans HCBT, TCBT/4 315 Ex on the network, 3x400V to operate exclusively in the star. For the installation of protective elements and thereby ensure safe operation of the fans are the ultimate basis of IN, Ia / In te and certificates listed in fans. Upon delivery, the fan must be checked carefully these values.

Speed control

The non-explosion fan are not suitable for control of the speed.

Additional Information
Weight [kg] 57
Availability out of sortiment
Manufacturer Soler & Palau
Type of good fan
Design duct, non-explosive
Min. temperature [°C] -40
Protection IP IP55