SA42625

PKI-C-EI90S-150-DV1

fire damper

Price
Excl. Tax: €46 Incl. Tax: €56
out of sortiment

The PKI-C-EI90S-150-DV1 fire damper is a fire shutter in HVAC circular ducts. The damper with fire resistance PKI-C-EI90S is mechanically closed by releasing the preloaded spring after melting of the fuse. The PKI-C cartridge fire damper marked "DV1" is equipped with a trigger spring and one limit microswitch signaling the "CLOSED / OPEN" blade position - voltage 24/230 V. The spring is released after melting of the fuse at 72 °C with a tolerance of approx. 1.5 °C. The fire damper must be located so that it can be accessed for regular inspections. The spacing between the HVAC ducts with the fire dampers must be at least 200 mm.


Min. temperature [°C]-10
Max. temperature [°C]65
Duct diameter [mm]150
Fire resistanceEI 90 S
Description
Installation The PKI-C fire damper can be installed as an element in the air ducts, with the axis of the damper blade after closing in the place of a fire dividing structure (wall / ceiling) or as an end element in the place of a fire dividing structure with an outlet to a disc valve. The fire damper must be mounted according to the manufacturer's installation instructions!
Additional Information
Replacement: SA238120
Weight [kg] 0.6
Availability out of sortiment
Manufacturer Systemair
Type of good damper
Design fire
Min. temperature [°C] -10
Fire resistance EI 90 S