CADBDIEKO2000

CADB-DI Ekonovent 2000

heat recovery unit

Price
Excl. Tax: €0 Incl. Tax: €0
on ask

The recovery unit CADB/CADT Ekonovent is designed for ventilation public areas, very powerful. A large number of options allows you to customize the space of instalation. Suitable for continuous operation.


Speed [min-1]1400
Air Flow Volume [m3/h]47
Current [A]8.6
Input Power [W]1100
Voltage heater230V
Heater power [kW]6
Current heater26 A
Max. temperature [°C]70
Protection IPIP22
Voltage230V
Noise [dB(A)]62
recuperation efficiency 93 %
Description
Housing

The housing is made of AL profile and sandwich panels about thickness 40 mm of galvanized varnished stainless sheet, fitted by thermal and noise insulation from polyurethane foam. The throats are equipped rubber seal. The drain of condesate is on side, where is exhaust air behind recovery changer.

Impeller

The impeller is centrifugal with backward cursed blades. Impeller is statical and dynamical balanced.

Motor

The engine, which is asynchronous with squirrel cage, thermal fuse is in winding the engine. The sizes of 1000 to 2000 single-phase 230V, three-speed, with starter capacitor, sizes of 4500 to 6000 three-phase 400V, single-speed. By size 3000 is both performance. By of 1000 to 3000 protection IP55, insulation of winding class F, by size of 4500 to 6000 protection IP20, insulation of winding class B.

Terminal block

All electrical equipment in a switchboards space inside the unit. On the surface of the unit is the only service switch.

Noise level

The overall sound pressure level emitted into the environment applies to the distance of 1.5 m from the casing and attached to the suction pipe. Total levels of acoustic power levels and in the middles of octave bands are s

Installation

The mounting in vertical position with throat above the other or horizontal with throat side by side. Next the unit is necessary have manipulation space for remove cover, filtres, changers and for performing periodic inspections of wiring. Under unit must be space for installing the siphon to drain condensate.

Additional Information
Weight [kg] 220
Availability on ask
Manufacturer Soler & Palau
Type of good heat recovery unit
Voltage heater 230V
Heater power [kW] 6
Current heater 26 A
Protection IP IP22
recuperation efficiency 93 %