- Description
-
Housing The housing is made of AL profile and sandwich panels about thickness 40 mm of galvanized varnished stainless sheet, fitted by thermal and noise insulation from polyurethane foam. The throats are equipped rubber seal. The drain of condesate is on side, where is exhaust air behind recovery changer.
Impeller The impeller is centrifugal with backward cursed blades. Impeller is statical and dynamical balanced.
Motor The engine, which is asynchronous with squirrel cage, thermal fuse is in winding the engine. The sizes of 1000 to 2000 single-phase 230V, three-speed, with starter capacitor, sizes of 4500 to 6000 three-phase 400V, single-speed. By size 3000 is both performance. By of 1000 to 3000 protection IP55, insulation of winding class F, by size of 4500 to 6000 protection IP20, insulation of winding class B.
Terminal block All electrical equipment in a switchboards space inside the unit. On the surface of the unit is the only service switch.
Noise level The overall sound pressure level emitted into the environment applies to the distance of 1.5 m from the casing and attached to the suction pipe. Total levels of acoustic power levels and in the middles of octave bands are s
Installation The mounting in vertical position with throat above the other or horizontal with throat side by side. Next the unit is necessary have manipulation space for remove cover, filtres, changers and for performing periodic inspections of wiring. Under unit must be space for installing the siphon to drain condensate.
- Additional Information
-
Weight [kg] 415 Availability on ask Manufacturer Soler & Palau Type of good heat recovery unit Protection IP IP22 recuperation efficiency 93 % - Download
-